Ducted Ventilation to Guestrooms from Corridors
Wednesday, November 26th, 2008Summary: The new codes now allow ducted guestroom ventilation for hotels in the west coast states which have now moved from the Uniform Building Code to the International Building Code. However, California has chosen to modify the IBC and continue to NOT ALLOW ducted ventilation to guestrooms without the use of fire/smoke dampers.
Discussion: The following code analysis is presented to document the conclusions stated in the summary above. This topic requires a step-by-step analysis of the code and there is really no short cut to what appears below. Just to be clear, the question is: Are fire/smoke dampers required at the penetration of the duct into the guestroom at the corridor wall?
Code Analysis:
1. The code defines four relevant types of separation that must be addressed as part of the code analysis. Those types are: Fire Barriers, Fire Partitions, Smoke Barriers, and Smoke Partitions.
2. Addressing each type of separation, we find the following:
b. Section 708 Fire Partitions: This applies to the separation of hotel sleeping units (guestrooms)
c. Section 709 Smoke Barriers: This section does not define where smoke partitions are required. It is silent regarding where the section is applied.
d. Section 710 Smoke Partitions: This section does not define where smoke partitions are required. It calls upon other sections to provide that definition.
3. Are smoke barriers and smoke partitions involved with guestrooms?
4. Section 706 requires ducts and air transfer openings comply with Section 716.
5. Section 708 requires ducts and air transfer openings comply with Section 716.
6. Section 716 addresses duct and air transfer openings of all types. Paragraph 716.6 Where Required defines where fire dampers, smoke dampers, and combination fire/smoke dampers are required for each type of separation. There are then two cases to analyze the hotel guestrooms. The first case is a duct routed in the corridor with taps to each guestroom through the corridor wall. This case involves crossing a Fire Barrier. The second case is a duct routed from guestroom to guestroom which involves crossing a Fire Partition. These two cases are analyzed below.
7. Duct Routed in Corridor: Since we know from above that guestroom separation from the corridor is a Fire Barrier, then the applicable sub-paragraph is 716.5.2 Fire Barriers:
b. Conclusion: The 2006 IBC allows air supply to guestrooms from a common duct in the corridor without fire dampers or smoke dampers as described above.
8. Duct Routed in Guestrooms: Since we know from above that guestroom separation is only a Fire Partition, then the application sub-paragraph is 716.5.4 Fire Partitions:
ii. Duct penetration is less than 100 square inches.
iii. Duct is 26 gage steel.
iv. No openings communicated to corridor.
v. Duct installed above a ceiling.
vi. Duct not terminated at the corridor wall.
vii. A 12 inch steel sleeve through the corridor wall is provided for the duct.
ii. Duct less than 100 square inches: We need 30 cfm of air per guestroom. A 10 by 10 duct (100 square inches) can deliver 500 cfm of air, which will serve 16 guestrooms. If the duct begins at the center of the hotel, this restriction is not a problem.
iii. 26 gage steel is standard.
iv. The duct would have no openings to the corridor since the corridor air system would be a separate system.
v. A ceiling would be provided for the corridor. This is not always the case, but would be necessary (and desirable) under these conditions.
vi. The duct could not be terminated at the corridor wall of the guestroom. This requires some form of soffit in the guestroom, which is easily accomplished. The grille can then be installed at the wall of the soffit.
vii. A 12 inch sleeve through the corridor wall is easily provided. The requirements for this sleeve are detailed further in the code.
9. California: In the California version of the 2006 IBC there is additional wording added to Paragraph 716.5.4. This wording states that the exception which allows the deletion of the fire/smoke dampers in the IBC DOES NOT APPLY in California for high rise buildings and Group R buildings. Hence, this exception is explicitly not allowed in California. The result is that fire/smoke dampers are required for a ducted ventilation supply system, which, of course, makes it cost prohibitive.
